In short: Add up the current draw of all 24 V actuators that run at the same time and add about 20 % reserve. The result is the minimum current of the power supply in amps. The VS-C24-7A control unit delivers up to 7 A and replaces a separate power supply in ventilation systems.
Skip the separate power supply: the VS-C24-7A control unit converts 230 V to 24 V, delivers up to 7 A and controls up to 7 actuators – €60 net (ventilation only, not a smoke vent control panel). Optional VS-C24-F-1 remote control €14 net. VS-C24-7A in the shop →
Matching 24 V actuators: VS-KA chain actuator from €65 · VS-LA linear actuator from €110 · VS-ZA 800 rack and pinion actuator from €105 (net).
The formula
Power supply current = total current draw of all actuators running simultaneously × 1.2
You get the power in watts by multiplying the current by 24 V. The current draw is on the rating plate or in the actuator's datasheet – for Vent Systems in the downloads area of the product page.
Worked example
A stairwell has four fanlights. According to the datasheet each actuator draws 1.0 A (example value). All four run together.
| Step | Invoice | Result |
|---|---|---|
| Total current draw | 4 × 1.0 A | 4.0 A |
| 20 % reserve | 4.0 A × 1.2 | 4.8 A |
| Performance | 4.8 A × 24 V | approx. 115 W |
| Fits the VS-C24-7A? | 4.8 A < 7 A | Yes |
If the actuators don't run at the same time, only the group that runs together counts. On the VS-C24-7A all connected actuators run together – for separate groups use one control unit per group.
Power supply or control unit?
- Pure power supply: provides 24 V only. To open and close you also need switches with polarity reversal or a control unit.
- VS-C24-7A control unit: converts 230 V to 24 V (max. 7 A) and drives the actuators open and closed by switch or radio. Rain and wind sensors can be connected. €60 net, in stock in Hamburg.
- SHEV systems: Here the approved smoke vent control panel powers the actuators. The VS-C24-7A is not a smoke vent control panel.
Don't forget the cable cross-section
At 24 V, noticeable voltage is lost over long cables. If too little reaches the actuator, it runs slower or stops. Estimate the voltage drop on a copper cable like this:
ΔU = 2 × cable length (m) × current (A) ÷ (56 × cross-section in mm²)
Example: 20 m cable, 3 A, 1.5 mm² gives about 1.4 V – just under 6 % of 24 V. With 2.5 mm² it is only about 0.9 V. The permissible voltage drop is in the actuator's datasheet; if in doubt, choose the larger cross-section.
What to look out for
- Only add up the actuators that really run at the same time.
- Inrush currents and ageing are reasons for the reserve – don't calculate too tightly.
- Mount the power supply or control unit dry and well ventilated.
- Never mix up 24 V and 230 V actuators: a 24 V actuator must not be connected to 230 V.
- The 230 V connection must be made by a qualified electrician.
Read more: Laying cables for window drives: cross-section, length and connection
Frequently asked questions
How many actuators can the VS-C24-7A handle?
Up to 7 actuators, depending on current draw. The total of all actuators must stay below 7 A.
Is a power supply with exactly the calculated total enough?
Better not. Plan for about 20 % reserve so the power supply delivers enough current reliably at start-up and after years of operation.
Where do I find my actuator's current draw?
On the rating plate or in the datasheet. For Vent Systems actuators it is in the downloads area of the product page.
Learn more: 24 V power supply in the glossary · Current consumption · Voltage drop · Cable cross-section · Planning a ventilation control · Controls in the shop.
See also in the glossary: Polarity reversal · Safety extra-low voltage (SELV)
How many actuators can the VS-C24-7A supply?
Calculated with a 20 % reserve; use the current draw from your actuator’s datasheet.
| Current per actuator | Max. actuators | Current incl. reserve |
|---|---|---|
| 0.5 A | 7 | 4.2 A |
| 0.6 A | 7 | 5.0 A |
| 0.8 A | 7 | 6.7 A |
| 1.0 A | 5 | 6.0 A |
| 1.2 A | 4 | 5.8 A |
| 1.5 A | 3 | 5.4 A |
| 2.0 A | 2 | 4.8 A |
The control unit has connections for up to 7 actuators and delivers up to 7 A. Ventilation only, not for smoke vents.