Does your Aumüller drive need to be replaced? For the PLA and PLS series spindle drives and for the Chain drives KS2, KS4 and KS15, there are matching alternatives from Vent Systems. The table compares the data directly.
Which Vent Systems drive replaces which Aumüller drive?
| Aumüller drive | Data (manufacturer) | Alternative from Vent Systems | Note |
|---|---|---|---|
| PLA6 (also older PL 6) | 24 V, 600 N, 6 mm/s, stroke 100–1200 mm, IP65 | VS-LA 600 N | |
| PLA8 | 24 V, 800 N, 10 mm/s, IP65 | VS-LA 800 N | |
| PLA10 (also older PL 10) | 24 V, 1000 N, 12.6 mm/s, IP65 | VS-LA 1000 N | |
| PLA101 | 24 V, 1000 N, 4.6 mm/s, IP65 | VS-LA 1000 N | |
| PLA16 / PLA116 | 24 V, 1600 N, IP65 | VS-LA 2000 N | |
| PLS15 | 24 V, 1500 N, 16 mm/s, stroke 300–1200 mm, IP54 | VS-LA 2000 N | |
| PLS30 | 24 V, 3000 N, 7.8 mm/s, IP54 | VS-LA 3500 N | |
| PLS50 | 24 V, 5000 N, 4 mm/s, stroke 200–750 mm, IP54 | VS-LA 5000 N | |
| KS2 (chain) | 24 V, 250 N, IP32 | VS-KA chain drive 250 N | also available in 230 V |
| KS4 (chain) | 24 V, 400 N, up to 13 mm/s, IP32 | VS-KA chain drive 400 N | |
| KS15 (chain) | 24 V, 1500 N, stroke 250–1000 mm, up to 17 mm/s, IP20 | VS-KA 1500 N or VS-KA 2500 | VS-KA 2500 with IP66 for humid environments |
Angaben zu Fremdprodukten nach öffentlich zugänglichen Herstellerunterlagen (Stand 2026), ohne Gewähr. Aumüller ist eine Marke ihres Inhabers; Vent Systems steht in keiner Verbindung zum Hersteller. Bitte Einbaumaß, Kraft und Steuerung vor dem Tausch prüfen.
How do I find the right alternative to my Aumüller drive?
Aumüller type designations are informative: for PLA and PLS, the number indicates the force class (e.g. PLA8 = 800 N). Choose the VS-LA with the same or higher force and the stroke of your previous drive. Aumüller spindle drives are available with strokes up to 1200 mm, the VS-LA up to 800 mm as standard – longer strokes on request.
What to consider when replacing a drive
- Force: The new drive should have at least the force of the old drive. If in doubt, choose the next higher level.
- Stroke: Keep the stroke of the old drive. It is usually stated on the type plate.
- Voltage: Connect 24 V drives only to 24 V control units or SHEV control panels, and 230 V drives only to 230 V.
- Speed for SHEV: As a rule, SHEV windows must be fully open within 60 seconds. For long strokes, check whether the running speed is sufficient.
- Zugelassene NRWG: Bei zugelassenen natürlichen Rauch- und Wärmeabzugsgeräten (NRWG nach EN 12101-2) kann ein Antriebstausch die Zulassung aufheben. Tausch nur nach Rücksprache mit dem Fensterhersteller oder einem Sachkundigen.
- Brackets and installation dimensions: The original manufacturers' brackets do not fit 1:1. Use Vent Systems brackets and check the installation dimensions using our data sheet (downloads on the product page).
- Control: Before the replacement, check whether the existing control unit or SHEV control panel can handle the current consumption of the new drive.
Is there a replacement for the Aumüller PLA8?
Yes, the VS-LA with 800 N, 24 V and IP65 protection matches the PLA8 in force and voltage. Select the stroke according to the type plate; mount it with Vent Systems brackets.
Does the replacement drive work with my Aumüller SHEV control panel?
Vent Systems drives operate at 24 V DC with polarity reversal, like most SHEV drives. Before the replacement, check whether the control panel can handle the current consumption, and coordinate SHEV applications with the installer.
Download the replacement table as a PDF
All comparisons for GEZE, Aumüller, Kingspan STG, D+H, WindowMaster and HAUTAU on three pages – to print out or for the workshop: replacement table for window drives (PDF)
Not sure which drive fits?
Schicken Sie uns ein Foto des Typenschilds und des Fensters. Wir nennen Ihnen den passenden Antrieb von Vent Systems – ab Lager Hamburg, Versand innerhalb von 24 Stunden. Telefon: 040 50694631.
GEZE, Aumüller and Kingspan are trademarks of their respective owners. Vent Systems is not affiliated with these manufacturers. The manufacturer data is taken from publicly available data sheets (as of October 2026) and is for comparison only.
Further manufacturers and a step-by-step guide can be found in our guide Replacing window drives.